Functions, monitoring, and protective functions
9.3 Extended functions
9.2.23.5

Overview of important parameters

• r8911
• r8931
• p8986
• p8987[0...1]
9.3
Extended functions
9.3.1
Technology controller
Description
The "technology controller" function module allows simple control functions to be
implemented, e.g.:
● Level control
● Temperature control
● Dancer roll position control
● Pressure control
● Flow control
● Simple control without higher-level control
● Tension control
The technology controller features:
● Two scalable setpoints
● Scalable output signal
● Separate fixed values
● Integrated motorized potentiometer
● The output limits can be activated and deactivated via the ramp-function generator.
● The D component can be switched to the system deviation or actual value channel.
● The motorized potentiometer of the technology controller is only active when the drive
pulses are enabled.
The technology controller is designed as a PID controller, whereby the differentiator can be
switched to the control deviation channel or the actual value channel (factory setting). The P,
I, and D components can be set separately.