Electrical installation
4.10 Signal connections
NOTICE
Damage or malfunctions through impermissible voltage values
If the back EMF is impermissible then damage and malfunctions may occur on the
components.
• The back EMF at the outputs may only be in the range between -15 V and +15 V.
NOTICE
Damage to motor in the event of incorrectly connected KTY temperature sensor
If a KTY temperature sensor is connected with incorrect polarity, it is not possible to detect
when the motor overheats. Overheating can cause damage to the motor.
• Connect a KTY temperature sensor with the correct polarity.
X540: Joint auxiliary voltage for the digital inputs
Table 4- 41
Max. connectable cross-section: 1.5 mm²
Note
Use of the power supply
This voltage supply is only for powering the digital inputs.
110
Terminal block X540
Terminal
Designation
8
+24 V
7
+24 V
6
+24 V
5
+24 V
4
+24 V
3
+24 V
2
+24 V
1
+24 V
Technical data
Voltage: +24 V DC
Max. total load current of +24 V auxiliary voltage for
terminals X540 and X541 combined: 150 mA
Continuously short-circuit proof
Operating Instructions, 07/2016, A5E00331449A