9.4.5

Thermal motor protection

9.4.5.1
Description
Description
The priority of thermal motor protection is to identify critical situations. Possible reactions can
be assigned (p0610) and used when alarm thresholds are exceeded to enable continued
operation (e.g., with reduced power) and prevent immediate shutdown.
● Effective protection is also possible without a temperature sensor (p0600 = 0 or
p4100 = 0). The temperatures of different motor components (stators, core, rotors) can be
determined indirectly using a temperature model.
● Connecting temperature sensors allows the motor temperature to be determined directly.
In this way, accurate start temperatures are available immediately when the motor is
switched on again or after a power failure.
9.4.5.2
Temperature sensor connection at the customer terminal block TM31
Temperature measurement via KTY
The device is connected to terminals X522:7 (Temp+) and X522:8 (Temp-) on the customer
terminal block (TM31) in the forward direction of the diode. The measured temperature is
limited to between –140 °C up to +188.6 °C and is available for further evaluation.
● Activating the motor temperature measurement via the external sensor: p0600 = 10
If the customer terminal block TM31 is present and on completion of commissioning, the
source for the external sensor is set to the customer terminal block (p0603 = {TM31}
r4105).
● Set the KTY temperature sensor type: p4100 = 2.
Temperature measurement via PTC
The connection is made to user terminal block (TM31) at terminal X522:7/8. The threshold
for changing over to an alarm or fault is 1650 Ω. If the threshold is exceeded, the system
switches internally from an artificially-generated temperature value of -50° C to +250° C and
makes it available for further evaluation:
● Activating the motor temperature measurement via the external sensor: p0600 = 10
If the customer terminal block TM31 is present and on completion of commissioning, the
source for the external sensor is set to the customer terminal block (p0603 = {TM31}
r4105).
● Set the PTC temperature sensor type: p4100 = 1.
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A
Functions, monitoring, and protective functions
9.4 Monitoring and protective functions
481