Electrical installation
4.10 Signal connections
X521 / X531: Encoder connection 2 for HTL/TTL encoder with open-circuit monitoring
Table 4- 50
Max. connectable cross-section: 1.5 mm²
Note
Operation of unipolar HTL encoders
When unipolar HTL encoders are used, A*, B*, and R* on the terminal block must be
jumpered with M_Encoder (X531).
Table 4- 51
Max. connectable cross-section: 1.5 mm²
Measuring current via temperature sensor connection: 2 mA
Accuracy of the temperature measurement:
1)
- KTY: ±7 °C (including evaluation)
- PT1000: ±5 °C (PT1000 tolerance class B according to EN 60751 including evaluation)
- PTC: ±5 °C (including evaluation)
120
Encoder connection X521
Terminal
Signal name
1
A
2
A*
3
B
4
B*
5
R
6
R*
7
CTRL
8
M
Encoder connection X531
Terminal
Signal name
1
P encoder 5 V/24 V
2
M encoder
3
-Temp
1)
4
+Temp
1)
5
Reserved, do not use
6
Reserved, do not use
7
Reserved, do not use
8
Reserved, do not use
Technical data
Incremental signal A
Inverse incremental signal A
Incremental signal B
Inverse incremental signal B
Reference signal R
Inverse reference signal R
Control signal
Ground via inductivity
Technical data
Encoder supply
Ground for encoder power supply
Temperature sensor KTY84-1C130 /
PT1000 / PTC
Temperature sensor KTY84-1C130 /
PT1000 / PTC
Operating Instructions, 07/2016, A5E00331449A