Installation
5.2 Electrical installation
Note
Use 75 °C wire for an ambient temperature of 40 °C or less and use 90 °C wire for ambient
temperature between 40 °C and 60 °C.
A correction factor of K = 0.71 has been used based on the following:
A maximum of four cables are laid side by side on a cable ladder.
The ambient temperature during cable operation is 30 °C.
(in accordance with EN 60204-1 and IEC 364-5-523)

Conductor cross-sections of the DI/DO, AI/AO terminal connecting cable

Table 5-8
Conductor cross-sections of the DI/DO, AI/AO terminal connecting cable
Limit value (mm
)
2
Recommended value (mm
NOTICE
To ensure that input/output precision is ≤ 1 %, it's recommended that the cable length be
less than (<) 5 m. If you don't have this precision requirement, use a cable which is less than
(<) 30 m.
36
DO (Digital Outputs)
≤ 1.2
)
1.0
2
DI (Digital inputs)
AI (Analog inputs)
≥ 0.1
≥ 0.1
0.25
0.25
Operating Instructions, 08/2011, A5E03453178 (this is not an order number)
AO (Analog outputs)
≥ 0.1
0.25
SINAMICS V10