Sensor Module Cabinet-Mounted Smc30 - Siemens SINAMICS G130 Operating Instructions Manual

Converter built-in units 75 kw-800 kw
Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

4.10.5

Sensor Module Cabinet-Mounted SMC30

4.10.5.1
Description
The SMC30 Sensor Module is used for determining the actual motor speed. The signals
emitted by the rotary pulse encoder are converted here and made available to the closed-
loop controller via the DRIVE-CLiQ interface for evaluation purposes.
In conjunction with SINAMICS G130 the following encoders can be connected to the SMC30
Sensor Module:
● TTL encoder
● HTL encoder
● KTY, PT1000 or PTC temperature sensor
Table 4- 44
Connectable encoders with supply voltage
Encoder type
HTL bipolar 24 V
HTL unipolar 24 V
TTL bipolar 24 V
TTL bipolar 5 V
TTL unipolar
Table 4- 45
Note
Prefer a bipolar connection
Because the physical transmission media is more robust, the bipolar connection should
always be used for HTL encoders. The unipolar connection should only be used if the
encoder type does not output push-pull signals.
Note
Only connect one encoder system
Only one encoder system may be connected to the encoder module, either at X520 or at
X521/X531. The corresponding unused interface must not be used.
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A
X520 (SUB-D)
X521 (terminal)
Yes
Yes
Yes
Yes
No
Maximum signal cable lengths
Encoder type
TTL
HTL unipolar
HTL bipolar
X531 (terminal)
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
Electrical installation
4.10 Signal connections
Open-circuit moni-
toring
Yes
No
Yes
Yes
No
Maximum signal cable length in m
100
100
300
Remote sense
No
No
No
To X520
No
113

Advertisement

Table of Contents
loading

Table of Contents