Siemens SINAMICS G130 Operating Instructions Manual page 102

Converter built-in units 75 kw-800 kw
Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

Electrical installation
4.10 Signal connections
Danger to life due to software manipulation when using exchangeable storage media
Storing files onto exchangeable storage media amounts to an increased risk of infection,
e.g. with viruses and malware. As a result of incorrect parameterization, machines can
malfunction, which in turn can lead to injuries or death.
• Protect files stored on exchangeable storage media from malicious software by with
Note
Possible plant standstill by withdrawing or inserting the memory card in operation
If the memory card is withdrawn or inserted during operation, then data can be lost, possibly
resulting in a plant standstill.
• Only withdraw and insert the memory card when the Control Unit is in a no-voltage
condition.
Note
Insertion direction for the memory card
Only insert the memory card as shown in the photo above (arrow at top right).
NOTICE
Memory card damage caused by electric fields or electrostatic discharge
Electrical fields or electrostatic discharge may result in the memory card being damaged
and so cause malfunctions.
• When removing and inserting the memory card, always observe the ESD regulations.
Note
Possible data loss when returning the Control Unit with memory card
When returning a defective Control Unit for repair or testing, the data on the memory card
(parameters, firmware, licenses, etc.) could be lost.
• Do not return the memory card as well, but rather keep it in a safe place so that it can be
inserted in the replacement unit.
Note
Please note that only SIEMENS memory cards can be used to operate the Control Unit.
102
WARNING
suitable protection measures, e.g. virus scanners.
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A

Advertisement

Table of Contents
loading

Table of Contents