Siemens SINAMICS G130 Operating Instructions Manual page 84

Converter built-in units 75 kw-800 kw
Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

Electrical installation
4.10 Signal connections
Connectors
The cables must be connected via PROFIBUS connectors as they contain the necessary
terminating resistors.
The figure below shows suitable PROFIBUS connectors with/without a PG/PC connector.
Bus terminating resistor
The bus terminating resistor must be switched on or off depending on its position in the bus,
otherwise the data will not be transmitted properly.
The terminating resistors for the first and last nodes in a line must be switched on; the
resistors must be switched off at all other connectors.
The cable shield must be connected at both ends over large-surface area contacts.
Note
Connector type
Depending on the connector type, the correct assignment of the connector must be ensured
(IN/OUT) in conjunction with the terminating resistor.
Figure 4-18
84
PROFIBUS connector
without PG/PC connection
6ES7972-0BA42-0XA0
Position of the bus terminating resistors
PROFIBUS connector
with PG/PC connection
6ES7972-0BB42-0XA0
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A

Advertisement

Table of Contents
loading

Table of Contents