Functions, monitoring, and protective functions
9.2 Drive functions
Note
Deactivated functions in simulation mode
The following functions are deactivated in the simulation mode:
• Motor data identification
• Motor data identification, rotating without encoder
• Pole position identification
No flying restart is carried-out for V/f control and sensorless closed-loop vector control.
Note
Activating binector output r0863.1 in the simulation mode
In the simulation mode, binector output r0863.1 is set = 1. Therefore, before activating the
simulation mode, check as to whether additional devices are switched on using the signal. If
necessary, the corresponding BICO interconnection should be temporarily removed.
Commissioning
Simulation is activated using p1272 = 1; the following pre-requisites must be fulfilled:
● The drive unit must have been commissioned for the first time (default: Standard
induction motors).
● The DC link voltage must lie below 40 V (observe the tolerance of the DC link voltage
sensing).
Alarm A07825 (simulation mode activated) must be output during simulation operation.
Parameter
• p1272
418
Simulation operation
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A