Siemens SINAMICS G130 Operating Instructions Manual page 452

Converter built-in units 75 kw-800 kw
Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

Functions, monitoring, and protective functions
9.3 Extended functions
Figure 9-13
Figure 9-14
Function diagram
FD 7950
FP 7951
FD 7954
FD 7958
Key control parameters
• p1155 = r2294 CI: Speed controller speed setpoint 1 [FP 3080]
• p2253 = r2224 Technology controller setpoint effective via fixed setpoint [FD 7950]
• p2263 = 1
• p2264 = r4055 Actual value signal X
• p2280 = Kp
• p2285 = Tn
• p2200 = 1
452
Level control: Application
Level control: Controller structure
Technology controller – fixed values, binary selection
Technology controller – fixed values, direct selection
Technology controller – motorized potentiometer
Technology controller – closed-loop controller
D component in fault signal [FD 7958]
Calculate P gain by means of optimization
Calculate integral time by means of optimization
Technology controller enabled
via AI0 of TM31 [FP 9566]
actual
Operating Instructions, 07/2016, A5E00331449A