Functions, monitoring, and protective functions

9.4 Monitoring and protective functions

9.4
Monitoring and protective functions
9.4.1
Protecting power components
Description
SINAMICS power modules offer comprehensive protection of power components.
Table 9- 12
General protection for power units
Protection against:
Overcurrent
1)
DC link overvoltage
1)
DC link undervoltage
1)
Short-circuit
1)
Ground fault
Line phase-failure detec-
tion
1)
The monitoring thresholds are permanently set in the converter and cannot be changed by the user.
1)
476
Protective measure
Monitoring with two thresholds:
First threshold exceeded
Second threshold exceeded
Comparison of DC link voltage with
hardware shutdown threshold
Comparison of DC link voltage with
hardware shutdown threshold
Second monitoring threshold checked
for overcurrent
Uce monitoring for IGBT module
Monitoring the sum of all phase cur-
rents
Response
A30031, A30032, A30033
Current limiting in phase U has responded.
Pulsing in this phase is inhibited for one pulse peri-
od.
F30017 -> OFF2 is triggered if the threshold is ex-
ceeded too often.
F30001 "Overcurrent" -> OFF2
F30002 "Overvoltage" -> OFF2
F30003 "Undervoltage" -> OFF2
F30001 "Overcurrent" -> OFF2
F30022 "Monitoring Uce" -> OFF2
After threshold in p0287 is exceeded:
F30021 "power unit: Ground fault" -> OFF2
Note:
The sum of all phase currents is displayed in
r0069[6]. For operation, the value in p0287[1] must
be greater than the sum of the phase currents when
the insulation is intact.
F30011 "Line phase-failure in main circuit" -> OFF2
Operating Instructions, 07/2016, A5E00331449A