Process data monitoring time (setpoint timeout)
The "Setpoint timeout" only applies for access to process data (40100 ... 40109, 40110 ...
40119). The "Setpoint timeout" is not generated for parameter data (40300 ... 40522).
Fieldbus interface:
In parameter p2040 you define the time for cyclic data exchange for process data.
Setting range: 0 ... 20 ms.
The time depends on the amount of data to be transferred and the control.
"Setpoint timeout" (F01910) is issued by the Modbus if p2040 is set to a value > 0 ms and no
process data is requested within this time period.
COMM BOARD (CBE20):
In parameter p8840 you define the time for cyclic process data exchange.
Setting range: 0 ... 20 ms.
The time depends on the amount of data to be transferred and the control.
"Setpoint timeout" (F08501) is issued by the Modbus if p8840 is set to a value > 0 ms and no
process data is requested within this time period.
6.11.8

Parameters, faults and alarms

Parameters
• p0978
• p2030
• p2040
• r2050[0...19]
• p2051[0...24] CI: IF1 PROFIdrive PZD send word
• r2053[0...24]
• r2054
• p8835
• p8839
• p8840
• r8850[0...19]
• p8851[0...24] CI: IF2 PZD send word
• r8853[0...24]
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A
List of drive objects
Fieldbus interface protocol selection
Fieldbus interface monitoring time:
CO: IF1 PROFIdrive PZD receive word
IF1 PROFIdrive diagnostics PZD send word
PROFIBUS status
CBE20 firmware selection
PZD interface hardware assignment
COMM BOARD monitoring time
CO: IF2 PZD receive word
IF2 diagnostics PZD send
6.11 Communication via MODBUS TCP
Operation
311