Tightening Torque For Connection Terminals; Cross-Sections For Power And Motor Cables - Siemens SED2 series Operating Instructions Manual

Variable speed drives
Hide thumbs Also See for SED2 series:
Table of Contents

Advertisement

Connection terminals of
SED2 frame size F, IP20,
with built-in EMC filter
34/126
Siemens Building Technologies
HVAC Products
View without cable entry guide
and without lower terminal connection plate
DC-
B-
L1
PE
4.3.6

Tightening torque for connection terminals

Frame size
Tightening torque
Nm
4.3.7

Cross-sections for power and motor cables

Input voltage range 200 V – 240 VAC, 3-phase
Output
Min. cross-
rating
section of
kW (hp)
supply cable
2
mm
(AWG)
0.37 (0.5)
1 (17)
0.55 (0.75)
1 (17)
0.75 (1)
1 (17)
1.1 (1.5)
1 (17)
1.5 (2)
1.5 (15)
2.2 (3)
2.5 (13)
3 (4)
4 (11)
4 (5)
4 (11)
5.5 (7.5)
4 (11)
7.5 (10)
10 (7)
SED2 variable speed drives
Electrical installation
DC+
DC+
DC+
R+
B
B
L2
L3
U
V
W
L1
L2
L3
A
B
1.1
1.5
Max. cross-
section of supply
cable
2
mm
(AWG)
2.5 (13)
2.5 (13)
2.5 (13)
6 (9)
6 (9)
6 (9)
10 (7)
10 (7)
10 (7)
35 (2)
EMC filter
Mains voltage inputs
5192Z09en
C
D
E
2.25
10 (max.) 10 (max.)
Min. cross-
Max. cross-
section of motor
section of motor
cable
2
mm
(AWG)
mm
1 (17)
1 (17)
1 (17)
1 (17)
1 (17)
1 (17)
1.5 (15)
4 (11)
4 (11)
10 (7)
F
50
cable
2
(AWG)
2.5 (13)
2.5 (13)
2.5 (13)
6 (9)
6 (9)
6 (9)
10 (7)
10 (7)
10 (7)
35 (2)
CM1U5192en
01.2002

Hide quick links:

Advertisement

Table of Contents
loading