Main Frequency Reference; Main Frequency Reference; Dip Switch S1 Analog Input Signal Selection - YASKAWA CIMR-JC4A0002BAA Quick Start Manual

J1000 compact v/f control drive 200 v class, three-phase input: 0.1 to 5.5 kw 200 v class, single-phase input: 0.1 to 2.2 kw 400 v class, three-phase input: 0.2 to 5.5 kw
Table of Contents

Advertisement

3.9 Main Frequency Reference

3.9

Main Frequency Reference

u

DIP Switch S1 Analog Input Signal Selection

The main frequency reference can either be a voltage or current signal input at terminal A1.
When using input A1 as a voltage input, set DIP switch S1 to "V" (right position, default
setting) and program parameter H3-01 to "0" (0 to +10 Vdc with lower limit) or "1" (0 to +10
Vdc without lower limit).
To use current input at terminal A1, set the DIP switch S1 to "I" and set parameter H3-01 =
"2" or "3" (4-20 mA or 0-20 mA).
Voltage Input
0 to 10 V
62
Table 3.11 Frequency Reference Configurations
Drive
+10.5 V
+V
20 mA current
Main speed frequency
A1
reference (voltage input)
Frequency reference
AC
common
Figure 3.19 DIP Switch S1
YASKAWA ELECTRIC TOEP C710606 26B YASKAWA AC Drive – J1000 Quick Start Guide
http://nicontrols.com
Current Input
+10.5 V
+V
4 to 20 mA input
20 mA current
or
Main speed
0 to 20 mA input
A1
frequency reference
(current input)
AC
Frequency
reference
common
DIP Switch S1
I
V
Drive