No.
U6-93
Online Duplex
U6-94
Online Speed
U6-95
Online Duplex
U6-97
OPT SPARE 4
U6-98
First Fault
U6-99
Current Fault
7
PROFINET Messaging
◆
PROFINET Overview
This section describes the communication profile used between the PROFINET I/O network and the option.
The option supports the PROFIdrive profile. Users can select between the control and status words according to
the PROFIdrive profile or use the Yaskawa-specific control and status words.
◆
PROFIdrive Communication Profile
■
The Control Word and the Status Word
The contents of the Control Word and the Status Word are detailed in
drive states are presented in the PROFIdrive State Machine
■
Frequency Reference
The Frequency reference is a 16-bit word containing a sign bit and a 15-bit integer. A negative reference
(indicating reverse direction of rotation) is formed by calculating the two's complement from the corresponding
positive reference. The reference value is the desired output frequency.
■
Output Frequency
Output Frequency is a 16-bit word containing the current output frequency (U1-02) of the drive.
Bit
Name
ON
0
OFF1
1
OFF2
2
OFF3
3
OPERATION_ENABLE
4
RAMP_OUT_ZERO
5
RAMP_HOLD
6
RAMP_IN_ZERO
7
RESET
YASKAWA SIEP C730600 89E PROFINET Technical Manual
Name
Table 7.1 Control Word for PROFIdrive Communication Profile
Value
Proceed to READY TO OPERATE.
1
Emergency OFF. Proceed to OFF1 ACTIVE; proceed further to READY TO SWITCH ON unless other
0
interlocks (OFF2, OFF3) are active.
Continue operation (OFF2 inactive).
1
0
Emergency OFF. Proceed to OFF2 ACTIVE; proceed further to SWITCH ON INHIBIT.
Continue operation (OFF3 inactive).
1
Emergency stop. Proceed to OFF3 ACTIVE; proceed further to SWITCH-ON INHIBIT.
0
1
Proceed to ENABLE OPERATION.
Inhibit operation. Proceed to OPERATION INHIBIT.
0
Normal operation. Proceed to RAMP FUNCTION GENERATOR: ENABLE OUTPUT.
1
0
Stop according to selected stop type.
Normal operation.
1
Halt ramping (Ramp Function Generator output held). Proceed to RAMP FUNCTION GENERATOR:
0
ENABLE ACCELERATOR.
Normal operation. Proceed to OPERATING.
Note:
1
This bit is effective only if the fieldbus interface is set as the source for this signal by drive
parameters.
0
Force Ramp Function Generator input to zero.
Fault reset if an active fault exists. Proceed to SWITCH ON INHIBIT.
0 -> 1
Description
Shows CN1 Port 1 duplex setting currently available.
Shows CN1 Port 2 link speed currently available.
Shows CN1 Port 2 duplex setting currently available.
Shows option software version.
Shows first option fault. Refer to page
Shows current option fault. Refer to page
Table 7.1
(Figure
7.1).
Proceed to STATE/Description
7 PROFINET Messaging
51
for more information.
51
for more information.
and
Table 7.2
respectively. The
Range
0: Half
1: Full
10: 10 Mbps
100: 100 Mbps
0: Half
1: Full
-
-
-
29