PROFINET Messaging

PROFINET Overview

This section describes the communication profile used between the PROFINET I/O network and the option.
The option supports the PROFIdrive profile. Users can select between the control and status words according to
the PROFIdrive profile or use the Yaskawa-specific control and status words.

PROFIdrive Communication Profile

The Control Word and the Status Word

The contents of the Control Word and the Status Word are detailed in
drive states are presented in the PROFIdrive State Machine

Frequency Reference

The Frequency reference is a 16-bit word containing a sign bit and a 15-bit integer. A negative reference
(indicating reverse direction of rotation) is formed by calculating the two's complement from the corresponding
positive reference. The reference value is the desired output frequency.

Output Frequency

Output Frequency is a 16-bit word containing the current output frequency (U1-02) of the drive.
Bit
Name
ON
0
OFF1
1
OFF2
2
OFF3
3
OPERATION_ENABLE
4
RAMP_OUT_ZERO
5
RAMP_HOLD
6
RAMP_IN_ZERO
7
RESET
YASKAWA SIEP C730600 89E PROFINET Technical Manual
Name
Table 7.1 Control Word for PROFIdrive Communication Profile
Value
Proceed to READY TO OPERATE.
1
Emergency OFF. Proceed to OFF1 ACTIVE; proceed further to READY TO SWITCH ON unless other
0
interlocks (OFF2, OFF3) are active.
Continue operation (OFF2 inactive).
1
0
Emergency OFF. Proceed to OFF2 ACTIVE; proceed further to SWITCH ON INHIBIT.
Continue operation (OFF3 inactive).
1
Emergency stop. Proceed to OFF3 ACTIVE; proceed further to SWITCH-ON INHIBIT.
0
1
Proceed to ENABLE OPERATION.
Inhibit operation. Proceed to OPERATION INHIBIT.
0
Normal operation. Proceed to RAMP FUNCTION GENERATOR: ENABLE OUTPUT.
1
0
Stop according to selected stop type.
Normal operation.
1
Halt ramping (Ramp Function Generator output held). Proceed to RAMP FUNCTION GENERATOR:
0
ENABLE ACCELERATOR.
Normal operation. Proceed to OPERATING.
Note:
1
This bit is effective only if the fieldbus interface is set as the source for this signal by drive
parameters.
0
Force Ramp Function Generator input to zero.
Fault reset if an active fault exists. Proceed to SWITCH ON INHIBIT.
0 -> 1
Description
Shows CN1 Port 1 duplex setting currently available.
Shows CN1 Port 2 link speed currently available.
Shows CN1 Port 2 duplex setting currently available.
Shows option software version.
Shows first option fault. Refer to page
Shows current option fault. Refer to page
Table 7.1
(Figure
7.1).
Proceed to STATE/Description
7 PROFINET Messaging
51
for more information.
51
for more information.
and
Table 7.2
respectively. The
Range
0: Half
1: Full
10: 10 Mbps
100: 100 Mbps
0: Half
1: Full
-
-
-