Main Frequency Reference; Main Frequency Reference; Dip Switch S1 Analog Input Signal Selection - YASKAWA CIMR-JA Series Installation & Start-Up Manual

Compact v/f control drive
Hide thumbs Also See for CIMR-JA Series:
Table of Contents

Advertisement

3.9

Main Frequency Reference

u

DIP Switch S1 Analog Input Signal Selection

The main frequency reference can either be a voltage or current signal input.
To use current input at terminal A1, set the DIP switch S1 to "I" (default setting) and set
parameter H3-01 = "2" or "3" (4-20 mA or 0-20 mA).
When using as a voltage input, set DIP switch S1 to "V" (right position) and program
parameter H3-01 to "0" (0 to +10 Vdc with lower limit) or "1" (0 to +10 Vdc without lower
limit).
Voltage Input
0 to 10 V
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
Table 3.11 Frequency Reference Configurations
Drive
+10.5 V
+V
20 mA current
Main speed frequency
A1
reference (voltage input)
AC
Frequency reference
common
Figure 3.19 DIP Switch S1

3.9 Main Frequency Reference

Current Input
+10.5 V
+V
4 to 20 mA input
20 mA current
or
Main speed
0 to 20 mA input
A1
frequency reference
(current input)
AC
Frequency
reference
common
DIP Switch S1
I
V
Drive
63
3

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cimr-jt seriesJ1000 series

Table of Contents