Technical Data; Generator Differential Protection Genpdif; Identification - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 048-UEN A
6.3.8
6.4
6.4.1
Technical manual
IEC05000301 V1 EN
Figure 48:
Logic diagram for 1Ph High impedance differential protection
HZPDIF

Technical data

Table 43:
HZPDIF technical data
Function
Range or value
Operate voltage
(20-400) V
I=U/R
Reset ratio
>95%
Maximum continuous
U>Trip
power
Operate time
10 ms typically at 0 to 10 x U
Reset time
100 ms typically at 10 to 0 x U
Critical impulse time
2 ms typically at 0 to 10 x U

Generator differential protection GENPDIF

Identification

Function description
Generator differential protection
2
/SeriesResistor ≤200 W
d
d
d
IEC 61850
identification
GENPDIF
Section 6
Differential protection
Accuracy
± 1.0% of I
r
-
-
-
-
-
IEC 60617
ANSI/IEEE C37.2
identification
device number
87G
I
>
d
SYMBOL-NN V1 EN