Chapter 2
Install the Dynamix 1444 Series Monitoring System
86
Self-generating Magnetic Sensor
The connected channel of the Tachometer Signal Conditioner must be
configured with:
• Transducer Type = Self-generating Magnetic Pickup, and
• Transducer Power = OFF
Wire the pickup as illustrated.
Figure 36 - Channel 0 Wiring for a Self-generating Magnetic Sensor
Shield Floating
* Shield can be landed to any available shield connection. See the IMPORTANT note on
Figure 37 - Channel 1 Wiring for a Self-generating Magnetic Sensor
Shield Floating
* Shield can be landed to any available shield connection. See the IMPORTANT note on
Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
24
18
3
Common
Signal
2
7*
Shield
1
7
page 56
for additional information.
24
18
6
Common
Signal
5
10*
Shield
1
7
page 56
for additional information.
19
13
6
12
7
2
3
19
13
6
12
10
5
6