Appendix A
CIP Objects
Dynamix Normal CM 

Data Object

464
This configures the Normal CM (Condition Monitoring) Data object (class
0x398). This data is dynamic data (TWF and FFT) which is captured as part
of the Trend and Alarm and Transient*Data capabilities of the module. 'Live'
data can also be requested direct from this object.
Available services allow for data requests for Normal CM data according to
requester specifications.
Table 197 - Object Instance
Instance ID
0
1...4
Table 198 - Class Attributes
Attribute
Access
NV
ID
Rule
1
Get
NV
16
Get
V
17
Get
V
Table 199 - Instance Attributes
Attribute
Access
NV
Name
ID
Rule
TWF and Common Parameters
16
Get
V
Enable
17
Get
V
Signal Source
18
Get
V
Number of
Averages
19
Get
V
Measurement
Units
20
Get
V
Associated Tacho
Source
21
Get
V
Waveform
Record Length
FFT Specific Configuration
Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
Description
Normal CM Data Class Instance
Instances 1...4 are respectively assigned to measurement channels 0...3
Name
Data
Description of
Type
Attribute
Revision
UINT
Current object revision.
Synchronization
SINT
A cross module
Enable
synchronization control.
Waveform/FFT
BYTE
Control of the way FFT/
Storage Format
TWF data is stored On
board the module.
Data
Description of
Type
Attribute
Group of six configuration attributes.
BYTE
Type of Normal CM data
to be enabled.
SINT
Defines the data source.
Same for both TWF and
FFT.
SINT
Default is FFT averaging
unless waveform
averaging is enabled in
attribute 16,.
ENGUNITS
Set the measurement
units that are based on
selected data source.
SINT
Tacho source selection.
SINT
Defines the number of
samples in the Normal
CM, waveform.
Group of 3 configuration attributes.
Semantics of
Values
Current revision.
Future use
Set at zero
Storage options
Fixed at 0x11
Semantics of Values
Enable control
Source selection
options
Averages: 1, 2, 3, 6, 12,
23, 45, 89, or 178
Engineering units
options
For tacho events
Index: 0...5