Allen-Bradley 1444-TSCX02-02RB User Manual page 391

Monitoring system
Table of Contents

Advertisement

Table 119 - SpecialRequest Description (CM Record Request Parameters)
Bit
0
SR_MAG_PHASE
1 and 2
Reserved
3
SR_FILTER_LO
4
SR_FILTER_HI
5
SR_EXTENDED
IMPORTANT
(1) The FMAX and FFT Lines presented in the AOP assume that bits 3, 4 and 5 are set. If other selections are made, then the FMAX or the number of FFT lines of a downloaded FFT does not always reflect
that presented in the AOP.
(2) When automatically deciding the factor to apply to decimated or synchronously resampled data, the firmware applies the SR_FILTER_LO (37.5%) factor when the -24 dB/octave filter is applied, and
the SR_FILTER_HI (62.5 %) factor with the -48 dB/octave or the -60 dB/octave filters are applied.
Data that is decimated on the Alternate Path always applies the -48 dB/octave filter. The applied filter on the primary path is the -24 dB/octave filter except when either of the Aeroderivative
Measurement Types are selected, in which case it applies the -60 dB/octave filter.
Byte Offset
Structure Member
Within Structure
0
SessionInstance
1
DynamicChannel
2
CompletedRecords
4
RecordSize
Description
Set to request phase (see
magnitude data is returned.
Set bit to specify that if samples are decimated, either by specifying a lower FMAX
resampling, then 37.5% of the unfiltered FFT lines are returned.
If bits 3 and 4 are both set, then the firmware automatically determines the number of returned FFT lines,
based on applied filtering.
Set bit to specify that if samples are decimated, either by specifying a lower FMAX
resampling, then 62.5% of the unfiltered FFT lines are returned.
If bits 3 and 4 are both set, then the firmware automatically determines the number of returned FFT lines,
based on applied filtering
Set bit to specify that if samples are not decimated or synchronously resampled that 112.5% of the unfiltered
FFT lines are returned.
When not set, 100% of FFT lines are returned for samples that are not decimated nor synchronously sampled.
Recommended use is to set bits 3, 4 and 5. This setting makes sure that in all cases the maximum number of
lines are returned that are, in all cases, free of any filter attenuation or potential aliasing effects.
Channel Select
Bit
0
Channel
0
The host sends the following CM Record Request Parameters as part of an
0x4C service request.
Data Type
Description
USINT
The host copies the SessionInstance returned here into each subsequent CM Record Request. Up to
three instances are supported.
USINT
Indicates the dynamic channel for this record. Channels 0 though 3 are valid channels.
UINT
Incremented each time that another complete record has been transferred.
There are often several packets per completed record.
UDINT
For a given session the RecordSize.
Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
Phase Data on page
334) and magnitude data from an FFT buffer, otherwise just
(2)
(2)
.
1
2
3
1
2
3
CIP Objects
Appendix A
(1)
or by synchronous
(1)
or by synchronous
4
5
6
Reserved
7
391