Chapter 4
Measurement Definition

Overall

Table 28 - Overall
Parameter
Overall (0) Signal Source
Overall (1) Signal Source
132
The Dynamic Measurement module of the Dynamix™ 1444 Series can measure
two Overall values per channel: Overall (0) and Overall (1). This page is used
to configure these measurements.
For non-multiplexed Module Personalities, see
Overall measurements update at a rate of not slower than every 40
milliseconds.
Values
Value is fixed as "Post Filter"
Value is fixed at "Mid Filter"
Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
Comment
The signal source for the first Overall measurement is fixed at the output of the Primary Signal
Path (Post-Filter). Overall (0) Signal Source is the fully filtered (LP and HP) and (if necessary)
integrated signal (see
Filters
page).
The signal source for the second Overall measurement is fixed at the output of the primary path
FMAX (decimation) function (Mid-Filter). The signal is reduced to any selected new sample rate
(FMAX), and has been low pass filtered (if defined). It has not been high pass filtered or
integrated.
General Page on page
97.