Dynamix Event Log Object - Allen-Bradley 1444-TSCX02-02RB User Manual

Monitoring system
Table of Contents

Advertisement

Appendix A
CIP Objects

Dynamix Event Log Object

406
The event log object (class code 0x38D) refers to a module-based event log,
where a history of key events can be held in NV memory - both alarm and
system events are retained. At least the last 6,500 event entries can be retained,
but note that an actual event can generate multiple log entries.
The event log referred to by this object is Dynamix module functionality,
independent of any Logix functions of the same, or similar name.
Table 135 - Object Instances
Instance ID
Description
0
Event Log Class Instance
Class Attributes
Attribute
Access Rule NV
ID
1
Get
8
Get
9
Get
10
Get
Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
Name
Data Type
NV
Revision
UINT
NV
Last Alarm
STRUCT
Time/Date
NV
Last Event
STRUCT
Time/Date
NV
Erase Cycles
UDINT
Description of Attribute
Current object revision.
Time Stamp of last Alarm logged.
Can be 16 bytes.
See
Table 143 on page
413.
Time Stamp of last Event logged.
Can be 16 bytes.
See
Table 143 on page
413.
Number of update erase cycles so
far.
< 100,000 advised.