Table 181 - Instance Attributes (continued)
19
Get
V
20
Get
V
21
Get
V
Alarm Thresholds
24
Get
V
25
Get
V
26
Get
V
27
Get
V
32
Get
V
33
Get
V
34
Get
V
35
Get
V
Adaptive Monitoring
40
Get
V
Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
Alarm Form
SINT
Defines form of alarm.
Alarm Type
SINT
Defines behavior
regarding TX OK state.
Alarm Processing
SINT
Defines alarm
Mode
processing mode to be
Normal, Adaptive, or
Profile.
Group of eight configuration attributes.
Low Alert
REAL
Defines low alert
Threshold
threshold limit that is
used for Under
Threshold and Window
alarm types.
High Alert
REAL
Defines high alert
Threshold
threshold limit that is
used for Over Threshold
and Window alarm
types.
Low Danger
REAL
Defines low danger
Threshold
threshold limit that is
used for Under
Threshold and Window
alarm types.
High Danger
REAL
Defines high danger
Threshold
threshold limit that is
used for Over Threshold
and Window alarm
types.
Hysteresis
SINT
The amount on the safe
side of a threshold by
which the value must
recover to clear the
alarm.
Delay/Sustain
DINT
Duration that a
Time (Alert)
measurement alarm
input must be
continuously present
before being reported
as an Alert alarm event
Delay/Sustain
DINT
Duration that a
Time (Danger)
measurement alarm
input must be
continuously present
before being reported
as a Danger alarm
event.
Alarm Multiplier
REAL
Indicates how the
thresholds are adjusted
when the alarm
(threshold) multiplier
function is invoked.
Group of eleven configuration attributes.
Adaptive
INT
The data source for the
Monitoring Source
control variable.
CIP Objects
Appendix A
Alarm form option
Alarm type
options
Alarm processing
options
Range: -
49000...48000
Range: -
48000...49000
Range: -50000
...49000
Range: -
49000...50000
Range: 0...20 %
Individual delays
are an integer in
ms
Range: 0...65500
Individual delays
are an integer in
ms
Range: 0...65500
1: in effect
disabled
>1: alarm less
likely
<1: alarm more
likely
Range: 0.01...to
100
Source selection