Attribute Semantics - Allen-Bradley 1444-TSCX02-02RB User Manual

Monitoring system
Table of Contents

Advertisement

Appendix A
CIP Objects
452

Attribute Semantics

Individual Alarm Status
Individual alarm status code can represent one or more of the following
conditions:
• Bit 0 - Alert usage enabled
• Bit 1 - Danger usage enabled
• Bit 2 - Adaptive mode
• Bit 3 - Profile mode
• Bit 4 - Multiplier configured
• Bit 5 - Multiplier active
• Bit 6 - Alert status
• Bit 7 - Danger status
Alarm Form
The following selection choices define the measurement alarm form.
Table 182 - Alarm Form
Value
0x00
0x01
0x02
0x03
Alarm Type
The following options define measurement alarm behavior that is related to
transducer status (TX OK).
Table 183 - Alarm Type
Value
0x00
0x01
0x02
Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
Description
(0) - Over Threshold
(1) - Outside Window
(2) - Under Threshold
(3) - Inside Window
Description
TX OK Considered - requires TX OK status to report alarm condition
TX OK Monitored - forces an alarm when TX status is NOK
TX OK Not Considered - Don't care about TX OK state