Allen-Bradley 1444-TSCX02-02RB User Manual page 440

Monitoring system
Table of Contents

Advertisement

Appendix A
CIP Objects
Table 173 - Instance Attributes
Attribute ID
Access Rule NV
1
Get
V
2
Get
V
Sensor Type Configuration
16
Get
V
17
Get
V
24
Get
V
25
Get
V
Trigger Configuration
32
Get
V
33
Get
V
34
Get
V
Sensor OK Detection
40
Get
V
41
Get
V
42
Get
V
43
Get
V
44
Get
V
TSC Output Configuration
48
Get
V
49
Get
V
440
NV status relates to nonvolatile storage in the auxiliary module, not in the
main module.
Name
Data Type
TSC Measured Speed Output
REAL
Individual Transducer Status
BYTE
Group of four configuration attributes.
Input Sensor Type
USINT
Input Name
SINT[32]
Sensor Power Supply
SINT
Sensor Target,
INT
Pulses Per Rev
Group of three configuration attributes.
Trigger Mode
SINT
Trigger Threshold
INT
Trigger Slope/Edge
SINT
Group of 5 configuration attributes.
Sensor OK Definition
BYTE
Sensor OK High Threshold
INT
Sensor OK Low Threshold
INT
High RPM Threshold
REAL
Low RPM Threshold
REAL
Group of 2 configuration attributes.
Tacho Bus and TSCX terminal
SINT
connections, output 0
TSCX terminal connections,
SINT
output 1
Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
Description of Attribute
Actual Speed considering number of
pulses per revolution.
Individual transducer-operating
status information.
Definition of input source that
configures required inputs and
signal conditioning.
Physical channel name identifier.
Bit-coded configuration for tacho
power supply configuration.
The number of signal pulses per
revolution of the shaft.
Potential support for auto threshold
detection on the TSC module.
Trigger detection threshold voltage
that is specified in mV
Definition of trigger detection slope. 0: Positive
TX OK Definition that drives the
appropriate OK line of the tacho bus.
High-voltage threshold for the
Sensor OK monitoring window.
Low voltage threshold for the Sensor
OK monitoring window
High RPM Threshold for the Sensor
OK monitoring window.
Low RPM Threshold for the Sensor
OK monitoring window.
Define processed signal type to be
output on the Tacho bus and
terminal output 0.
Define processed signal type to be
output via terminal interface.
Semantics of Values
RPM
Selection options
32 characters
TX power supply options
1...255
0: Configured threshold
1: Auto detection
(when implemented)
Range: -23000...23000
(+23V)
1: Negative
Configuration options
mV
Range: -24000...24000
mV
Range: -24000...24000
RPM
Range: 50...30000
RPM
Range: 0.5...29000
0: 1/rev signal
1: multi-pulse (raw) signal
Fixed at 0.
0: 1/rev signal
1: multi-pulse (raw) signal
Fixed at 0.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents