Allen-Bradley 1444-TSCX02-02RB User Manual page 523

Monitoring system
Table of Contents

Advertisement

Table 278 - Relay Expansion Module 2 / Expansion Module Communications Status
Bit
Description (Expansion Relay Module 2) Bit
0
Relay module not responding. If set
disregard other bits in this group.
1
Module is configured (so normally expected
set).
2
Code CRC fault.
3
High temperature warning.
4
Link/bus fail.
5
Halt is active.
6
RAM fault.
7
RAM access error.
8
Relay 0 not inhibited (so normally set).
9
Relay 1 not inhibited.
10
Relay 2 not inhibited.
11
Relay 3 not inhibited.
12
Relay 0 drive failure.
13
Relay 1 drive failure.
14
Relay 2 drive failure.
15
Relay 3 drive failure.
Status Response Codes
0: Normal / no exception.
1: Invalid command / command not recognized.
2: Not used.
3: Message 2 and message 1 data content does not agree.
4: Not used.
5: No message 1 data was received (send only if message 2 data is received).
6: Module not configured.
7: Not used.
Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
CIP Objects
Description (Expansion Relay Module 1)
16
Relay module 0 (address 1) status.
17
18
19
Relay module 1 (address 2) status.
20
21
22
Relay module 2 (address 3) status.
23
24
25
Analog Output module status.
26
27
28
Tachometer Signal Conditioner module
status.
29
30
31
Spare
Appendix A