Allen-Bradley 1444-TSCX02-02RB User Manual page 285

Monitoring system
Table of Contents

Advertisement

Tag
Activated
Disabled
Latching
Alarming
Bypassed
SetPointMultActive
FirstOut
VotedAlarmInstance0
VotedAlarmInstance1
VotedAlarmInstance2
VotedAlarmInstance3
VotedAlarmStatus0
VotedAlarmStatus1
Inp0MeasAlarmState
Inp0MeasAlarmXdcrOK
Inp1MeasAlarmState
Inp1MeasAlarmXdcrOK
Inp2MeasAlarmState
Inp2MeasAlarmXdcrOK
Inp3MeasAlarmState
Inp3MeasAlarmXdcrOK
SpeedGateActive
SpeedGateXdcrOK
LogixGate0Active
LogixGate1Active
LogixGate2Active
LogixControlActive
ModuleFaultOrBypass
Table 67 - Alarm Status
Description
Activated One or more associated relay outputs (and status indicators) are set
Disabled Alarm is disabled
Latching Configured as latching
Alarming Required conditions for the "alarm state" are true
Bypassed Alarm is bypassed (associated relays / status indicators that are held in non-alarm state
Set Point Multiplier is active
First Out Set if the first alarm to activate since last Reset or Bypass
4 bit value.
The number of the Voted Alarm that the status refers to.
Value is 1...13, which references voted alarm 0...12 (so, is Voted Alarm number + 1).
2 bit value.
Voted Activate Status to Activate On: 0=Normal, 1=Alert, 2=Danger, 3=TX Fault
Input Measurement Alarm 0 State of the measurement alarm that is referenced for alarm input 0(1)
Input Measurement Alarm 0 TX OK TX OK status of the measurement alarm that is referenced for alarm input 0
Input Measurement Alarm 1 State of the measurement alarm that is referenced for alarm input 1(1)
Input Measurement Alarm 1 TX OK TX OK status of the measurement alarm that is referenced for alarm input 1
Input Measurement Alarm 2 State of the measurement alarm that is referenced for alarm input 2(1)
Input Measurement Alarm 2 TX OK TX OK status of the measurement alarm that is referenced for alarm input 2
Input Measurement Alarm 3 State of the measurement alarm that is referenced for alarm input 3(1)
Input Measurement Alarm 3 TX OK TX OK status of the measurement alarm that is referenced for alarm input 3
Speed Gate Status 0 = not gating, 1 = gating
Speed Gate TX OK TX OK status of the input that is used for speed gating
Indicates that the first of the up to three gate controls is set.
Gate control can be defined using the output tags AlarmControl0/1 and the Discrete Inputs Pt0 and Pt1.
Indicates that the second of the up to three gate controls is set.
When multiple gate controls are defined, the gate is TRUE when all controls are set
Indicates that the third of the up to three gate controls is set.
When multiple gate controls are defined, the gate is TRUE when all controls are set
Indicates that Logic Control is set.
Alarm Logic can be controlled (forced true) using output tags AlarmControl0/1 or either Discrete Input Pt0 or Pt1.
Indicates that the relay is being bypassed, if configured to trip on bypass, or that the module is in fault, if the relay is
configured to trip on module fault.
The alarm number is presented in the assembly in bit format. The alarm
instance is the decimal value that is represented by the 4 bits. For example:
-test:I.AlarmStatus[0].VotedAlarmInstance0
-test:I.AlarmStatus[0].VotedAlarmInstance1
-test:I.AlarmStatus[0].VotedAlarmInstance2
-test:I.AlarmStatus[0].VotedAlarmInstance3
Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
Operate the Module
Chapter 10
0
1
0
0
285