Dynamix Data Manager Object - Allen-Bradley 1444-TSCX02-02RB User Manual

Monitoring system
Table of Contents

Advertisement

Appendix A
CIP Objects
Table 110 - Configuration Group 29 (continued)
Source Object
Source Instance
0x38C
1
Dynamix Data Manager
Object
Table 113 - Instance Attributes
Attribute ID
Access
NV
Rule
1
Get
V
2
Get
V
3
Get
V
4
Get
V
5
Get
V
6
Get
V
384
Source Attribute ID
31
64
65
66
67
The Data Manager Object(class code 0x38B) defines the setup, data storage,
and data access for Dynamix Trend and Dynamix Alarm data records. The
Normal CM Data Object (0x398) configures which dynamic data is available
to the Data Manager Object.
Table 111 - Object Instances
Instance ID
0
1
Table 112 - Class Attributes
Attribute ID Access Rule NV
1
Get
Name
Data Type
Trend Data-Set Usage
BYTE
Trend Data-Set Status
BYTE
Trend Overall Data Records
UINT
Trend Dynamic Data Record Sets
UINT
Alarm Data-Set Usage
USINT
Alarm Data-Set Status
WORD
Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
Name
Extra Startup Sample Time
DWORD 0 (Transient Static Data Source)
DWORD 1(Transient Static Data Source)
DWORD 2 (Transient Static Data Source)
DWORD 3 (Transient Static Data Source)
Description
Data Manager Class Instance
Data Manager Setup Instance
Name
NV
Revision
Description of Attribute
Not implemented - fixed at zero
Returns the current operational
mode
Returns the number of static data
records that the buffer
Returns the number of dynamic
data records that the buffer
currently holds.
Not implemented
Returns the current operational
status.
Data Type
INT
DWORD
DWORD
DWORD
DWORD
Description of Attribute
Defines revision of Dynamix Data
Manager Object
Semantics of Values
Use attribute 24
Bit 0 is set when the Low-Resolution
Overall Trend records are cycling
Bit 1 is set when the High-Resolution
Overall Trend records are cycling
Bit 2 is set when the FFT dynamic records
are cycling
Bit 3 is set when the TWF dynamic records
are cycling
Bits 4 to 7 are not used
"Cycling" means that the buffer has filled
and is now overwriting earlier entries.
Fixed depth: 641
Fixed depth: 64
Use attribute 24
See Alarm Data-Set Status in Attribute
Semantics

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents