Terminal
Name
49
RET_1
50
RET_1
51
+24V_1
52
+24V_1
53
RET_0
54
RET_0
55
+24V_0
56
+24V_0
57
OVR
58
OVR
59
Shield
60
Shield
61
Shield
62
Shield
63
Shield
64
Shield
Main Module Connectors
These connections provide duplicate terminals for twin, wide ranging DC
supplies (24V nominal).
56
55
54
+24V-0
+24V-0
RET_0
You can use the duplicate terminals to daisy chain the power from one base to
the next (subject to an overall current limit and using a star connection to avoid
excessive voltage drop). There is internal diode protection against reverse
polarity and for the purposes of automatic supply selection when redundant
sources are connected to inputs 0 and 1. The supply side connections are
isolated from the remainder of the module circuitry.
Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
Install the Dynamix 1444 Series Monitoring System
Application
Description
Module Power
Supply 1 Return
Supply 1 +24V
Supply 0 Return
Supply 0 +24V
Buffered Outputs
Override High
Override Low
Shield
Cable shield connection points
53
52
51
RET_0
+24V-1
+24V-1
Chapter 2
50
49
RET_1
RET_1