The following information applies when operating this equipment in
hazardous locations:
Products that are marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division
2 Groups A, B, C, D, hazardous locations, and nonhazardous locations only. Each product
is supplied with markings on the rating nameplate to indicate the hazardous location
temperature code. When products are combined within a system, the most adverse
temperature code (lowest "T" number) can be used to help determine the overall
temperature code of the system. Combinations of equipment in your system are subject
to investigation by the local Authority Having Jurisdiction at the time of installation.
WARNING:
Explosion Hazard -
• Do not disconnect equipment unless power has been removed or
the area is known to be nonhazardous.
• Do not disconnect connections to this equipment unless power
has been removed or the area is known to be nonhazardous.
Secure any external connections that mate to this equipment by
using screws, sliding latches, threaded connectors, or other
means that are provided with this product.
• Substitution of components can impair suitability for Class I,
Division 2.
• If this product contains batteries, they must only be changed in
an area that is known to be nonhazardous.

Electrical Safety Considerations

WARNING: To comply with the CE Low Voltage Directive (LVD), all power connections to this
equipment must be powered from a source compliant with the following:
• Safety Extra Low Voltage (SELV), or
• Protected Extra Low Voltage (PELV) 
To comply with UL/CUL requirements, this equipment must be powered from a source compliant
with the following:
• Limited Voltage Supply
If the input power supply is restricted to 8 A, no additional protection is necessary. However, for
supplies with higher current ratings that serve multiple groups of main modules, the first
module of the daisy chain requires an 8 A current limiting fuse for protection.
WARNING: All wiring must comply with applicable electrical installation requirements (for
example, N.E.C. article 501-4(b)).

North American Hazardous Location Approval

Informations sur l'utilisation de cet équipement en environnements
dangereux:
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une utilisation en
environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux.
Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent
le code de température pour les environnements dangereux. Lorsque plusieurs produits
sont combinés dans un système, le code de température le plus défavorable (code de
température le plus faible) peut être utilisé pour déterminer le code de température
global du système. Les combinaisons d'équipements dans le système sont sujettes à
inspection par les autorités locales qualifiées au moment de l'installation.
Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
Install the Dynamix 1444 Series Monitoring System
AVERTISSEMENT:
Risque d'Explosion -
• Couper le courant ou s'assurer que l'environnement est classé
non dangereux avant de débrancher l'équipement.
• Couper le courant ou s'assurer que l'environnement est classé
non dangereux avant de débrancher les connecteurs. Fixer tous
les connecteurs externes reliés à cet équipement à l'aide de vis,
loquets coulissants, connecteurs filetés ou autres moyens fournis
avec ce produit.
• La substitution de composants peut rendre cet équipement
inadapté à une utilisation en environnement de Classe I, Division
2.
• S'assurer que l'environnement est classé non dangereux avant de
changer les piles.