Connecting Speed Signals across Modules

When an external signal is used to serve multiple DYN modules, the
recommended wiring solution is as follows.
1. Wire the source signal to the TTL inputs on the first module, per
Inputs on page
66.
2. On the first module, wire one of its outputs to the TTL inputs. (#1) on
the next module per
page
58.
Example of wiring Discrete Output 0 to Tacho Input 0
Example of wiring Discrete Output 1 to Tacho Input 1
3. Daisy chain additional modules by repeating
4. To output the TTL signal the wired opto-isolated output must be
configured to replicate the "Local TTL Tach 0 Input" or "Local TTL
Tach 1 Input", as appropriate. See
page
111.
Use this method to daisy chain the external TTL signal to be sure that there is
isolation between modules. See
information.