Output Configuration Page; Page Overview - Allen-Bradley 1444-TSCX02-02RB User Manual

Monitoring system
Table of Contents

Advertisement

Chapter 6
Configure Analog Outputs

Output Configuration Page

200

Page Overview

Table 42
is a list of the different output configurations.
Table 42 - Output Configuration
Parameter
Values
Enable
Enabled (checked) or Not
Enabled (not checked)
Measurement
Available selections are
dependent on the
Channel Type and the
Channel Measurement
Type for the channel that
is associated with each
measurement.
See Define Module
Functionality page in
Module Definition on
page 92
Configuration on
page
See
Table 43 on page 201
to view all available
settings.
Low Engineering
Any
High Engineering
Any
Units
Fault Mode Output State Select from:
• No action
• < 4 mA
• > 20 mA
Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
Comment
Check the box to enable output from each respective
4...20 mA output channel.
Select the measurement to be output on the referenced
Analog Module channel.
and
Hardware
112.
Enter the value, in Engineering Units, which is to
correspond to an output magnitude of 4 mA.
Enter the value, in Engineering Units, which is to
correspond to an output magnitude of 20 mA.
Displays the Engineering Units for the selected
measurement.
Select the desired behavior on fault.
Outputs the measured value, regardless of the fault
condition.
If "< 4 mA" the output is driven to 2.9 mA.
If "> 20 mA" the output goes to ~21 mA.
Faults that result in the defined behavior include:
• Transducer Fault (for the channel that is associated with
the measurement)
• Expansion Bus Failure
• Expansion Module Self-Check Fail