Opto Output Source
An index that allows for source selection.
Table 262 - Opto Output Source
Bit
Description
0
OFF
1...13
Voted Alarm Instance 1...13
Output Type: Alert
14...16
Reserved
17...29
Voted Alarm Instance 1...13
Output Type: Danger
30...32
Reserved
33...45
Voted ALARM INSTANce 1...13
Output type: TX OK
48
Local TTL Tacho Input 0
49
Local TTL Tacho Input 1
50
Tacho Bus 0
51
Tacho Bus 1
52
Tacho Bus OK 0
53
Tacho Bus OK 1
54
Local Logic Input 0
55
Local Logic Input 1
56
TX 0 Fault
57
TX 0 Fault
58
TX 0 Fault
59
TX 0 Fault
127
Module Status/OK
Indices 48...53 are routed directly in hardware, all other selections are actively
controlled, based on the state of the source selected.
The local relay control allows for Module Fault to be to some extent,
configurable on a per relay basis. Index 127 follows the first definition of
module fault (first relay, so usually the main module relay configuration).