Measurement Object

Table 159 - Instance Attributes
Attribute ID
Access Rule
NV
1
Get
V
2
Get
V
3
Get
V
DC Measurement
16
Get
V
17
Get
V
18
Get
V
19
Get
V
426
The DC Measurement Object (0x391) defines configuration of DC overall
measurement by selecting smoothing constants, and definition of measurement
units. One instance is linked to each available transducer channel and is fully
separate from the DC Volts overall value
Table 157 - Object Instances
Instance ID
0
1...4
Table 158 - Class Attributes
Attribute
Access
ID
Rule
1
Get
8
Get
Name
Data Type
DC Value
REAL
Rod Drop Value
REAL
DC Bias
REAL
Group of 5 configuration attributes
DC Measurement Units
ENGUNITS
DC Measurement TC
REAL
DC Measurement Offset
REAL
DC Measurement Sense
SINT
Control
Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
Description
DC Measurement Class Instance
DC measurement setup and data for channels 0...3
• Instances 1 for transducer channel 0, DC measurement
• Instances 2 for transducer channel 1, DC measurement
• Instances 3 for transducer channel 2, DC measurement
• Instances 4 for transducer channel 3, DC measurement
NV
Name
Data
Type
NV
Revision
UINT
V
Enabled Instances
STRUCT
BYTE
BYTE
BYTE
Description of Attribute
Processed DC measurement output.
Processed rod-drop value output.
Measured in DC Volts.
The same as attribute 1 of the
Transducer Object
The DC measurement units.
Time
constant
definition for
DC
measurement
(demanded).
Measurement offset in selected
measurement units.
Sense control of the DC measurement
for axial/thrust applications.
Description of
Semantics of
Attribute
Values
Current object revision.
Current revision.
Bit-wise coding of
Decoding
enabled DC
information.
measurement instances.
Active instances for
channels 0...3.
Reserved for full
multiplexing.
Reserved for full
multiplexing.
Semantics of Values
0 when rod drop
application is not active
for this channel
Options and selection
criteria
Range: 0.1...60 s, default
of 1
Is added to the
measurement.
Range: -50000...50000
0: Active/Normal
1: Inactive/Counter