If a reset is required, see
module is inhibited and does not have any established connections.
2. Update the firmware using ControlFLASH.
• An established class 1 connection must be normally closed. To close
the connection, you inhibit the module by executing a normal
shutdown of the controller, or cycle power on the module.
• After updating the module, verify that the module firmware has been
successfully updated.
While ControlFLASH reports the new version, the version reported
is only that of the auxiliary processor. However, the module has two
processors; an auxiliary processor and a Digital Signal Processor
(DSP), which also has firmware.
Firmware revisions are shown in
revision of both processors, and of any connected expansion
modules, can be viewed from the AOP Status page.
Figure 92 - Module Firmware
IMPORTANT The Status page is only updated when the AOP is in RUN mode.
See
Firmware Update Error Handling on page 248
errors in firmware updates are handled.
Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
Resetting the Module on page
Table 78 on page
Operate the Module
Chapter 10
241. Make sure that the
306. The firmware
for information on how
247