Configure Alarms
Chapter 8
Fail-Safe
The voted alarm fail-safe definition is not used by the voted alarm (logic).
Rather, it is inherited by any relays that reference the alarm (see
Relay Page on
page
203).
When defined as fail-safe, the coil of the relay is energized when not in an
alarm condition, and de-energized when it is in the alarm condition. This
provision is to make sure that upon loss of power that the relay moves to its
"safe" condition, which is assumed to be its position when in alarm.
Relays are the final element of the 1444 series Alarm Management System.

Relays

While the voted alarm can act as a "virtual relay", it cannot switch off power to
a motor. Also, the voted alarm cannot route power to a light or other
annunciator, or control a solenoid valve that can trip a turbine.
Also, in applications that require API-670 compliance, relays are the only
approved interface between the monitor system and the emergency shutdown
system or final actor when used to initiate a forced shutdown.
See
Relay Page on page 203
for an overview on how to use relays in the 1444
series system.
Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
229