Allen-Bradley 1444-TSCX02-02RB User Manual page 401

Monitoring system
Table of Contents

Advertisement

Table 128 - 0x4F Transient Record Request
Byte Offset
Structure Member
Within Structure
0
BufferSelect
2
RequestedCount
4
SessionInstance
5
ChannelSelect
Also note that a data communication session starts at the first service request
and ends after the final response of the exchange. However, it is subject of an
(inactivity) timeout of 30 seconds.
Table 127 - Object Specific Services
Service
Implementation
Code
Class
Instance
0x4B
x
x
0x4C
x
x
0x4D
x
x
0x4E
x
x
0x4F
-
x
0x4F Transient Record Request
Transient data is retrieved using a series of request/response unconnected
messages. One service is used to both start and continue with a session. The
first request initiates the session and subsequent requests return values that the
service returns. When the packet count down value that is returned reaches 0,
the session is completed.
The instance and attribute can be set to 1, but they are ignored.
The host sends the following Transient Record Request Parameters as part of
an 0x4F service request. This process is identical to the Data Manager Object
(0x38B), Service 0x4C CM Buffer Upload. Both services call the same service
handling code. That code is why the buffer select codes do not overlap with the
codes for the Data Manager Object.
Data Type
Description
INT
Specify the buffer to retrieve the data from:
• eOVERALL_TD0 (10), eFFT_TD0 (11),
• eTWF_TD0 (12), eTACHOL_TD0 (13),
• eOVERALL_TD1 (14), eFFT_TD1 (15),
• eTWF_TD1 (16), eTACHOL_TD1 (17),
• eOVERALL_TD2 (18), eFFT_TD2 (19),
• eTWF_TD2 (20), eTACHOL_TD2 (21),
• eOVERALL_TD3 (22), eFFT_TD3 (23),
• eTWF_TD3 (24), eTACHOL_TD3 (25)
The BufferSelect does not change during a session.
UINT
RequestedCount = 0 returns all records in the buffer.
RequestedCount = 1 returns the most recently collected record.
Any other positive count returns that number of records from the buffer. If the count is greater than the max
available records, the max available records is returned instead.
The RequestedCount does not change during a session.
USINT
The SessionInstance is initially specified as 0, but on subsequent calls the SessionInstance returned in CM
Record Response must be passed here.
BYTE
4 Bits indicating the source channel. The ChannelSelect does not change during a session.
This field is ignored for all overall buffer types (eOVERALL_TD0, eOVERALL_TD1, eOVERALL_TD2,
eOVERALL_TD3)
Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
Service Name
Description of Service
Reset transient buffer 0
Buffer-specific controls
Reset transient buffer 1
Reset transient buffer 2
Reset transient buffer 3
Transient Buffer Upload
See "0x4F Transient Record Request"
CIP Objects
Appendix A
401