Appendix A
CIP Objects
462
Logic Gating Source
Bit
Description
0
Local Logic Input 0
1
Local Logic Input 1
2
Logic Gating Service Request (0)
3
Logic Gating Service Request (1)
4...7
Reserved
8
gate0_control in the controller output table
9
gate1_control in the controller output table
0x00 defines Logic gating as disabled.
Up to three sources are allowed with multiple configured sources and logic
applied.
Logic Gating and Control Sense
Default behavior is logic gating/control is true when:
• Local Logic Input is low (based on logic input being pulled high)
• Logic control bit is high (1)
Assumes single defined source, OR logic situations.
Table 196 - Common Services
Service
Implementation
Code
Class
Instance
0x05
x
x
0x0E
x
x
No Object Specific Services are supported.
Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
Service Name
Description of Service
Reset
Reset the peak hold speed (RPM - max)
Get Attribute Single
Returns the contents of the specified attribute