The designated opto output is inactive in the following circumstances:
• OFF
• No alarm
• Tacho OK
• Logic input open
• TX OK
• Module Status OK
Note therefore that as inactive equals shelf state, they are non-fail-safe.
For the local tacho inputs, the opto is inactive when the input signal is high
(above the 2.5V threshold).
For the TSCX tacho inputs the opto is inactive when the input signal is LOW
(below the configured threshold).
Source Selection
The DSP FFT can be sourced from one of the first four sources or the last one
when those particular processing elements are configured as active (Channel
Set Up Object).
Index
Source
0x00 (0)
ADCOUT - Select ADC output stream (raw sampled data)
0x01 (1)
Pre-Filter - Before application-specific filters (and potentially after application-
specific signal pre-processing)
0x02 (2)
Mid-Filter - Selected mid Filter identifies inclusion of application Low Pass Filter
0x03 (3)
Post-Filter - Selected post Filter identifies inclusion of both application Low and High
Pass Filter including potentially enabled integration stages
0x04 (4)
Alternate path - A CM, alternate processing, path available when so configured in
the Channel Set Up Object
Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
CIP Objects
Appendix A
513