ProtectionLoopTimeWarning
Protection Loop Time Warning
MainModuleSummary
Main Module Summary Fault
Description (if = 1)
DSP critical alarms loop cycle time >100 milliseconds. If set, module does not satisfy performance requirements of
API-670.
Tag is considered in MainModuleSummary fault if Compliance Mode set to API-670.
Summary fault bit for the main module. The status bit is set if any of the following status indicators are set:
DSP Dual Port Memory Fault
Non-recoverable Fault
+1.5V Power Supply OK
+1.6V Power Supply OK
DSP 3.3V Power Supply OK
5V Power Supply OK
25.5V Power Supply OK
+24V Power Supply OK
25.5 Power Supply OK
-24V Power Supply OK
AD Ch0&1 +6.5V Power Supply OK
AD Ch0&1 +5V Reference OK
AD Ch0&1 Monitored Power OK
AD Ch2&3 Monitored Power OK
DSP Memory Fault
DSPCRCError
DSPReset
CalFault
CalTimeout
MainRelayFault
ProtectionLoopTimeWarning
+5VA Power Supply Fault
+24V Power Supply Fault
-24V Power Supply Fault
Also see
Summary Status Tags
on page 265.
Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
Operate the Module
Tag is hidden. Its state can be resolved from the DSP
status tag.
Tag is hidden. Its state can be resolved from the DSP
status tag.
Power supply status tags are normally set
Tag is hidden. Its state can be resolved from the DSP
status tag.
See
Table 54 on page
269.
Tag is hidden. Its state can be resolved from the DSP
status tag.
Chapter 10
271