Dynamix Voted Alarm Object

This voted/complex alarm object (class object 0x397) defines the
configuration of multiple input voted measurement alarms, the resulting alarm
behavior, and provides access to the associated logical alarm status.
Class attributes and services allow for alarm history information.
Table 185 - Object Instances
Instance ID
0
1...13
Unused instances exist and are accessible but have a disabled state.
Table 186 - Class Attributes
Attribute
Access
NV
Name
ID
Rule
1
Get
NV
Revision
8
Get
V
Instances
9
Get
V
Common Alert
10
Get
V
Common
Danger
11
Get
V
Common TX
Fail
12
Get
V
First Out Alarm
13
Get
V
Alarm History
16
Get
V
Trip Inhibit/
Bypass Source
17
Get
V
Alarm Reset
Source
Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
Description
Voted Alarm Class Instance
Voted Alarm object instances 1...13
Data
Description of Attribute
Type
UINT
Current object revision.
WORD
Defines the enabled voted
alarm instances.
BOOL
Boolean status indicates the
presence of at least one alert
condition.
BOOL
Boolean status indicating
presence of at least one
danger condition.
BOOL
Boolean status indicates the
presence of at least one TX
Fail condition.
STRUCT
Record of first logical alarm
event (Time Stamp,
measurement output, alarm
status) logged after reset of
First Out alarm option.
STRUCT
Array of events (Time Stamp,
measurement output, alarm
status) that represents last x
number of entries. A change
in the alarm status triggers
an entry.
BYTE
Source definition for Trip
Inhibit/Bypass
BYTE
Source definition for Reset
function
CIP Objects
Appendix A
Semantics of
Values
Current revision.
Bit coding (13 used)
Source selection
Source selection