102 mm
(4.92 in.)
25 mm
(1 in.)
158 mm
(6.22 in.)
System Space and Clearance Requirements
Design and layout of the system enclosures is a key consideration in any
installation. Verify that there is sufficient space for access to (and fitting/
removal of ) the top and bottom connectors, and a wiring/cable ducting
scheme that maintains appropriate separations.
For proper airflow and installation of the module, the following minimum-air
space requirements must be maintained around the system.
Figure 2 - Clearance Requirements
54 mm
(2.13 in.)
The 50 mm/2 in. clearance above and below the modules, in combination with
45° angled, pluggable connections, provides for:
• Use of tooling to make/remove electrical connections
• Visible wire identification
• Sufficient physical space to insert/remove pluggable connections
• Optimized air volume per module in relation to thermal performance
Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
Install the Dynamix 1444 Series Monitoring System
50 mm
(2 in.)
50 mm
Height: 125 mm (4.92 in.)
(2 in.)
Chapter 2
25 mm
(1 in.)
33