Chapter 2
Install the Dynamix 1444 Series Monitoring System
42
When you install the system, follow these instructions and install/configure
the components in this order.
1. Review the safety instructions.
2. Review the network connectivity considerations.
3. Review the system design guidelines, considerations, and requirements.
4. Mount the terminal base.
5. Establish expansion bus connections between modules.
6. Configure the main terminal base.
7. Configure the Auxiliary relay terminal base.
8. Configure the Auxiliary 4
9. Configure the Auxiliary TSC terminal base.
10. Install the module.
11. Configure the main module connectors.
12. Configure the main module transducers.
13. Configure the expansion module connectors.
14. Start the module and perform a self-test.
Figure 5 - Expansion Terminal Base – Overview
PID label area
DIN rail set screws (two ea)
Left EXP bus connector
Address switches
Bottom set screws (two ea)
Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
20 mA terminal base.
...
Upper base connector
Right EXP bus
Base-to-module
connector
PID label area
Module type label area
Lower base connector