Chapter 10
Operate the Module
Tag (continued)
MaxSpeed0Event
New Max Speed Detected Speed 0
MaxSpeed1Event
New Max Speed Detected Speed 1
RedundantSpeedFault
Redundant Speed Active
Tag
Ch0CalFault
Channel 0 Calibration Fail
Ch1CalFault
Channel 1 Calibration Fail
Ch2CalFault
Channel 2 Calibration Fail
Ch3CalFault
Channel 3 Calibration Fail
Tag
ExpRelay0Status
Expansion Relay 0 (address 1) Status
ExpRelay0OverTemperature
Relay Module 0 Over Temperature Warning
ExpRelay0Relay0NotInhibited
Relay Module 0 Relay 0 Not Inhibited
ExpRelay0Relay1NotInhibited
Relay Module 0 Relay 1 Not Inhibited
ExpRelay0Relay2NotInhibited
Relay Module 0 Relay 2 Not Inhibited
ExpRelay0Relay3NotInhibited
Relay Module 0 Relay 3 Not Inhibited
ExpRelay0Relay0Fault
Relay Module 0 Relay 0 Fault
ExpRelay0Relay1FaultRelay Module 0 Relay 1 Fault
ExpRelay0Relay2Fault
Relay Module 0 Relay 2 Fault
ExpRelay0Relay3Fault
Relay Module 0 Relay 3 Fault
274
Description (if=1)
Max Speed 0/1 Event. A new maximum speed is detected on Speed 0/1. Bit toggles when a new event is
detected.
Redundant tachometer mode is set and the tachometer has switched due to a tachometer failure
(Speed 0/1 Fault).
Table 57 - A/D Status
Description (If=1)
Hardware fault. See
Calibration on page
Table 58 - Relay Module Status
Description (if = 1)
Expansion Relay Module 0 (Address 1)
Container value allows access to hidden tags. The hidden tags provide no user actionable information. They are
provided to assist device diagnostics only.
See the
Assembly Object
(class code 0x04), on page 517, for the assembly members and bit assignments.
Indicates when the processor board temperature is less than -20 °C (-4 °F) or greater than 70 °C (158 °F). While the
module rating is based on surrounding air temperature, depending on airflow, the board temperature can exceed the
surrounding air temperature by up to 25 °C (77 °F). This difference means that it is possible that the alarm limit could
be exceeded when the surrounding air temperature is as low as 45 °C (113 °F). Consequently, the indication is
considered only a warning.
Normally set. Indicates that the relay is not inhibited. Goes unset (0) when TripInhibit = 1 or HW control Trip Inhibit/
Bypass is set (all enabled relays are inhibited).
Relay drive test has failed.
Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
292.