Dynamix Channel 

Setup Object

418
Where the sensor is a negatively powered Eddy Current Probe, the module
performs two additional checks:
• The transducer power supply that is provided by the module is
delivering at least 2 mA
• The transducer DC/bias voltage remains negative
These two checks are based on hardware monitoring, which is designed to
detect any discrepancy quickly, and are referred to as 'wire-off ' detection. Once
a wire-off condition has been detected, this failure is latched for 30 seconds.
Any recurrence that causes this timer to be restarted, such that recovery from a
wire-off condition, is 30 seconds after the last detected event. This measure
aims to make sure that signals have stabilized.
Table 147 - Common Services
Service
Implementation
Code
Class
Instance
0x0E
x
x
The Channel Setup Object (class code 0x38F) defines the basic sample rate,
decimation, and filter cutoff frequencies and alternate path processing for each
of the channels.
Table 148 - Object Instances
Instance ID
Description
0
Channel Setup Class Instance
1...4
Instances 1...4 define the setup for channels 0...3
Table 149 - Class Attributes
Attribute
Access
NV
ID
Rule
1
Get
NV
8
Get
V
Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
Service Name
Description of Service
Get Attribute Single
Returns the contents of the specified attribute
Name
Data
Description of
Type
Attribute
Revision
UINT
Current object
revision.
Enabled Instances
WORD
Bit-coding of
enabled instances.
Semantics of Values
Current revision.
Decoding information.