Time Sync Object

Table 292 - Instance Attributes
Attribute
Access
ID
Rule
1
Get/Set
2
Get
3
Get
4
Get
5
Get
6
Get/Set
7
Get
8
Get
9
Get
10
Get
The Time Sync Object (class code 0x43) provides a CIP interface to the IEEE
1588 Standard for a Precision Clock Synchronization Protocol for Networked
Measurement and Control Systems. This is commonly referred to as the
Precision Time Protocol or PTP.
Table 290 - Object Instances
Instance ID
0
1
Table 291 - Class Attributes
Attribute
Access
ID
Rule
1
Get
2
Get
NV
Name
NV
PTPEnable
IsSynchronized
SystemTimeMicroseconds
SystemTimeNanoseconds
OffsetFromMaster
maxOffsetFromMaster
MeanPathDelayToMaster
Grand MasterClockInfo
ParentClockInfo
LocalClockInfo
Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
Description
Class Instance of the CIP Time Sync Object
Active instance of the CIP Time Sync Object
NV Name
Data Type
NV
Revision
UINT
Maximum Instance
UINT
Data Type
Description of Attribute
BOOL
BOOL
ULINT
ULINT
LINT
ULINT
LINT
STRUCT
USINT[8]
ClockIdentity
UINT
ClockClass
UINT
TimeAccuracy
UINT
OffsetScaledLogVariance
UINT
CurrentUtcOffset
WORD
TimePropertyFlags
UINT
TimeSource
UINT
Priority1
UINT
Priority2
STRUCT
USINT[8]
ClockIdentity
UINT
PortNumber
UINT
ObservedOffsetScaledLogVari
ance
UDINT
ObservedPhaseChangeRate
STRUCT
USINT[8]
ClockIdentity
CIP Objects
Appendix A
Description of
Semantics of
Attribute
Values
Revision of Object
Revision 3
One Instance is supported
1
Semantics of
Values
Default = 1/Enabled
1: Synchronized
Microseconds
Nanoseconds
Nanoseconds
Nanoseconds
Nanoseconds
Encoded MAC ADDR.
0...255 (0: best)
Index values
lower = best
seconds
Atomic, GPS, Radio
Encoded MAC ADDR.
Encoded MAC ADDR.