Configure Relays
Table 44 - Relays
Parameter
Main Module Relay – Enable
Main Module Relay – Voted Alarm Number
Main Module Relay – Alarm Status to Activate On
Main Module Relay – Module Fault
Main Module Relay – Tach Fault
Main Module Relay – Communication Fault
Main Module Relay – Expansion Module Fault
Main Module Relay – Expansion Bus Fault
Main Module Relay – Latch Enable
Expansion Module Relay – Enable
Expansion Module Relay – Voted Alarm Number
Expansion Module Relay – Alarm Status to Activate On
204
Values
Checked (1) / Unchecked (0)
Blank or 0...12 presented in a list of enabled Voted
Alarms
Select from:
• Alert
• Danger
• Xdcr Fault
• Disarm
• Module Fault
Checked (1) / Unchecked (0)
Checked (1) / Unchecked (0)
Checked (1) / Unchecked (0)
Checked (1) / Unchecked (0)
Checked (1) / Unchecked (0)
Checked (1) / Unchecked (0)
Checked (1) / Unchecked (0)
Blank or 0...12 presented in a list of enabled Voted
Alarms
Select from:
• Alert
• Danger
• Xdcr Fault
• Disarm
• Module Fault
Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
Help
Check to enable the relay.
This value is the Voted Alarm that is associated with the
main module relay. If blank, then at least one fault must
be selected to act on.
Alert, Danger, and Transducer Fault are states that the
Voted Alarm can actuate on (see
Voted Alarms
If Disarm is selected, the relay is in Bypass mode.
If Module Fault is selected, then the relay actuates only on
the specified faults (not just Module Fault).
Check this value when the relay must actuate on a fault in
the main module.
When Fail-Safe Enable is checked for the selected Voted
Alarm, if Alarm Status to Activate On is set to Module Fault
this control is checked and disabled.
If the relay is configured to actuate on Module Fault only,
so no associated voted alarm, then the relay is configured
Fail Safe (normally energized).
Check this value when the relay must actuate on a
tachometer fault.
This fault actuates if a tachometer fault is indicated on any
enabled speed input (see
Speed
Page).
Check this value when the relay must actuate on an
Ethernet network fault.
Check this value when the relay must actuate on a fault
reported by in any connected expansion module.
Check this value when the relay must actuate on a fault of
the Expansion Bus.
Check this value when the relay must latch after having
actuated on any of the selected fault conditions.
Latch control for the alarm input is included in the Voted
Alarm definition.
Check to enable the relay.
This value is the Voted Alarm that is associated with the
expansion module relay. If blank, then at least one fault
must be selected to act on.
Alert, Danger, and Transducer Fault are states that the
Voted Alarm can actuate on (see
Voted Alarms
If Disarm is selected, the relay is in Bypass mode.
If Module Fault is selected, then the relay actuates only on
the specified faults (not just Module Fault).
Page).