Chapter 2
Install the Dynamix 1444 Series Monitoring System
56
Shield Connections
By design, the module is isolated from ground. All shield connections on this
connector and the lower base connector are common to one another (a "shield
bus"), but otherwise isolated.
64
63
62
Shield
Shield
Shield
Shield connections are provided as a termination point for cable screens/
shields, one or more can be used to connect the shield bus to a local ground of
your choice.
IMPORTANT When working with the shield bus, remember the following:
• The shield bus of each main and expansion module must be individually
connected to ground by at least one shield pin that is wired directly to
ground.
• For installations where EMI problems are identified, or are anticipated,
wire cable shields directly to ground rather than to the shield bus of the
module.

Upper Module Connector

Terminal
Name
33
NO
34
C
35
NC
36
SPARE
37
O1L
38
O1H
39
O0L
40
O0H
41
RET
42
BUFF3
43
RET
44
BUFF2
45
RET
46
BUFF1
47
RET
48
BUFF0
Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
61
60
59
Shield
Shield
Shield
Application
Description
Relay Outputs
Normally Open
Common
Normally Closed
Do not connect
Opto-isolated Outputs
Output 1 Low
Output 1 High
Output 0 Low
Output 0 High
Buffered Outputs
Channel 3 Return
Channel 3 Signal
Channel 2 Return
Channel 2 Signal
Channel 1 Return
Channel 1 Signal
Channel 0 Return
Channel 0 Signal