Temperature Transmitter - Allen-Bradley 1444-TSCX02-02RB User Manual

Monitoring system
Table of Contents

Advertisement

Chapter 2
Install the Dynamix 1444 Series Monitoring System
72
A list of appropriate terminals for each channel follows.
Typical Core Designation
Acceleration SIG (+)
Return (-)
Then link these terminals:
Temperature SIG (+)

Temperature Transmitter

Configure the channel for a +24V supply. A load resistor is required at the
input terminals to provide the necessary current/voltage conversion. In
addition to resistance value and precision (functional requirements), consider
resistor power rating as it pertains to heating and maximum surface
temperature under normal and fault conditions.
A list of appropriate terminals for each channel follows.
Typical Core Designation
Power
Return (-)
Fit Load Resistor
Complete the configuration as follows:
• Configure the sensitivity as: Load R * 16/TX Range (millivolt/
(1)
degree)
• Set an appropriate offset so 4 mA = 0°
(1) For slightly higher accuracy, include the effect of the channel input resistance.
Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
Channel 0
Channel 1
3
7
4
8
1 and 2
5 and 6
-
-
Channel 0
Channel 1
1
5
2
6
3 and 4
7 and 8
Channel 2
Channel 3
-
-
-
-
-
-
11
15
Channel 2
Channel 3
9
13
10
14
11 and 12
15 and 16

Hide quick links: