Table 47 - Voted Alarms
Parameter Name
Alarm Name
Alarm Status to Activate On – Alert
Alarm Status to Activate On – Danger
Alarm Status to Activate On – Transducer Fault
Measurement Alarm – Input 0
Measurement Alarm – Input 1
Measurement Alarm – Input 2
Measurement Alarm – Input 3
The module provides 13 voted alarms.
As with any alarm, a voted alarm is configured with specific inputs and logic
that assesses to a simple true/false (1/0) condition.
Values
Characters
Checked (1) / Unchecked (0)
Checked (1) / Unchecked (0)
Checked (1) / Unchecked (0)
All Measurement Alarms
All Measurement Alarms, except the Measurement Alarm
that is selected for Input 0
All Measurement Alarms, except the Measurement Alarms
selected for Inputs 0 and 1
All Measurement Alarms, except the Measurement Alarms
selected for Inputs 0, 1 and 2
Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
Configure Alarms
Comments
Enter a name up to 32 characters. There are no rules for the
names content or uniqueness. However, the name is used
when selecting Voted Alarms as input to other functions,
such as Relay definitions, so unique names are
recommended. Additionally the name:
• Must start with a letter or underscore ("_")
• Must consist of letters, numbers, or underscores
• Cannot contain two contiguous underscore characters
• Cannot end in an underscore
Check if Measurement Alarms with a status of Alert are
evaluated as TRUE when used as inputs to this Voted
Alarm.
If Alarm Status Alignment is set to Static (Module
Definition, General Page), then a Voted Alarm can specify
just one Alarm Status to Activate On.
Check if Measurement Alarms with a status of Danger are
evaluated as TRUE when used as inputs to this Voted
Alarm.
If Alarm Status Alignment is set to Static (Module
Definition, General Page), then a Voted Alarm can specify
just one Alarm Status to Activate On.
Check if Measurement Alarms with a status of Transducer
Fault are evaluated as TRUE when used as inputs to this
Voted Alarm.
If Alarm Status Alignment is set to Static (Module
Definition, General Page), then a Voted Alarm can specify
just one Alarm Status to Activate On.
Select the Measurement Alarm to use in Instance 0 of the
Voted Alarm logic.
If the Voted Alarm is enabled and this input is included in
the specific Logic, then the Measurement Alarm that is
referenced by this Input must be enabled.
Select the Measurement Alarm to use in Instance 1 of the
Voted Alarm logic.
If the Voted Alarm is enabled and this input is included in
the specific Logic, then the Measurement Alarm that is
referenced by this Input must be enabled.
Select the Measurement Alarm to use in Instance 2 of the
Voted Alarm logic.
If the Voted Alarm is enabled and this input is included in
the specific Logic, then the Measurement Alarm that is
referenced by this Input must be enabled.
Select the Measurement Alarm to use in Instance 3 of the
Voted Alarm logic.
If the Voted Alarm is enabled and this input is included in
the specific Logic, then the Measurement Alarm that is
referenced by this Input must be enabled.